Toon

Product details
Manufacturer: Quby
Brand: Eneco
Product identification: 6500-1200-2000
Product description:

Energy Management Display which also acts as an OpenTherm thermostat

product_512caed51074a

Company
Company name: Quby B.V.
City: AMSTERDAM
Country: NETHERLANDS
Interfaces
Interface 1 (Master)
Functions and Features
general: standard
ch: otc control
ch: roomtemp control
dhw: setpoint adjustment
dhw: eco/comfort
ID's
ID0:HB0: Master status: CH enable
ID0:HB1: Master status: DHW enable
ID0:HB3: Master status: OTC active
ID0:HB5: Master status: Summer/winter mode
ID0:HB6: Master status: DHW blocking
ID0:LB0: Slave Status: Fault indication
ID0:LB1: Slave Status: CH mode
ID0:LB2: Slave Status: DHW mode
ID0:LB3: Slave Status: Flame status
ID0:LB6: Slave Status: Diagnostic/service indication
ID1: Control Setpoint i.e. CH water temperature Setpoint (°C)
ID2:HB0: Master configuration: Smart power
ID2:LB: Master MemberID Code
ID3:HB0: Slave configuration: DHW present
ID3:HB1: Slave configuration: Control type
ID3:HB4: Slave configuration: Master low-off&pump control
ID5:HB0: Service request
ID5:HB1: Lockout-reset
ID5:HB2: Low water pressure
ID5:HB3: Gas/flame fault
ID5:HB4: Air pressure fault
ID5:HB5: Water over-temperature
ID5:LB: OEM fault code
ID6:HB0: Remote boiler parameter transfer-enable: DHW setpoint
ID6:HB1: Remote boiler parameter transfer-enable: max. CH setpoint
ID6:LB0: Remote boiler parameter read/write: DHW setpoint
ID14: Maximum relative modulation level setting (%)
ID15: Maximum boiler capacity (kW) / Minimum boiler modulation level(%)
ID16: Room Setpoint (°C)
ID17: Relative Modulation Level (%)
ID18: Water pressure in CH circuit (bar)
ID24: Room temperature (°C)
ID25: Boiler flow water temperature (°C)
ID26: DHW temperature (°C)
ID27: Outside temperature (°C)
ID28: Return water temperature (°C)
ID35: Boiler fan speed Setpoint and actual value
ID48: DHW Setpoint upper & lower bounds for adjustment (°C)
ID56: DHW Setpoint (°C) (Remote parameter 1)
ID57: Max CH water Setpoint (°C) (Remote parameters 2)
ID73: An OEM-specific diagnostic/service code for ventilation / heat-recovery system
ID113: Number of un-successful burner starts
ID114: Number of times flame signal was too low
ID115: OEM-specific diagnostic/service code
ID116: Number of succesful starts burner
ID117: Number of starts CH pump
ID118: Number of starts DHW pump/valve
ID119: Number of starts burner during DHW mode
ID120: Number of hours that burner is in operation (i.e. flame on)
ID121: Number of hours that CH pump has been running
ID122: Number of hours that DHW pump has been running or DHW valve has been opened
ID123: Number of hours that burner is in operation during DHW mode
ID127: Slave product version number and type